PowerPanel™ Business Edition
88
If the Center establishes the communications with below devices, refer to SNMP Community and SNMP
Trap Community sections for further details.
z UPS RMCARD201
z PDU with a model name of PDU20SW8RNET or PDU15SW8RNET
Secret Phrase
The Secret Phrase is used to create secure network communications between Client, Agent, UPS
RMCARD202 and PDUs with a model name other than PDU20SW8RNET or PDU15SW8RNET. The default
phrase is powerpanel.encryption.key. The Secret Phrase can be configured on the
Security/Authentication page in the PowerPanel Applications, or on the System/Security page in the PDU
and UPS RMCARD web. The Secret Phrase which is used in the PowerPanel Applications, PDU and UPS
must match.
Note: If the firmware version on the RMCARD202 is earlier than 1.1, you should refer to SNMP Community
and SNMP Trap Community sections for the correct configurations.
SNMP Community
The Center uses this community to authenticate communication between the PDU and UPS in order to
access their information. The default community is private. The community can be configured on the
Network/Access Control page in the UPS remote management card (RMCARD) web or on the
Network/SNMP Settings page in the PDU web. By default, the PDU/UPS uses private as the community
with write permission, and public with read only permission. The community used by the Center to access
the PDU/UPS must have write permission for an administrative power control.
SNMP Trap Community
The Center uses the community to authenticate the SNMP trap from the monitored PDU and UPS RMCARD.
The community default is public. The IP address of the Center computer must be added to the Trap Receiver
list on the Network/Trap Notification page of the UPS RMCARD and the PDU to ensure that the community
must match.
Note: The SNMP community is limited to 15 characters in the PDU and UPS RMCARD.
Note: If you have firewall software installed, configure the settings to allow access through port 3052
(UDP/TCP), port 53568 (TCP), port 162 (UDP) and port 53566(UDP). These ports must open because the
Center uses them to establish the communication with PDU and UPS RMCARD.
Network
Please refer to Security/Network section about how to configure Network settings.